Multiple VFD Pumps to Common Header
I have an application where I have 4 variable speed pumps that can supply feedwater to a common header that in turn feeds up to 4 industrial boilers. It takes up to 3 of these pumps operating in parallel to handle the load of all 4 boilers. There is also a smaller, constant speed pump used for very low loads. The pumps are not identical, 2 are motor driven and 2 are turbine driven. Our goal is to maintain a constant header pressure. I would like suggestions on how to control the speed on the pumps over the load range, including cutting in and out pumps as required. Pump starting and stopping will be manual by operators based on some alert.
The previous comments should be most helpful, but I would want to also
consider the type of turbines used and the reasons for using them. Is
there some process use for the exhaust steam from the turbines
(presuming that these are steam turbines)? It seems possible that the
use of the steam pumps could alter the operation and economics of the
connected system. Do the boilers serve a common header, are they all
the same size, capacity, etc.?
If these turbines are of the size
range that I am assuming (relatively small compared to multi-thousand
horsepower units), their heat rate probably implies substantial relative
energy costs compared to the electrically powered pumps.
Another
question that comes to mind is the load profile for these pumps. If
most of the time the load is great enough for the electrically powered
pumps to operate at or near full speed, then the adjustable speed
drives' losses simply represent a needless parasitic loss, and constant
speed drive for these could make more sense for both initial and
operating costs.
From the information provided, it seems likely
that the turbine driven pumps would probably be best kept in reserve for
emergencies and high load periods, and the electrically powered pumps
probably do not need to have adjustable speed drives. This would allow
simplification (and substantial savings) in the control system both
initially and long-term. (Boiler feed pump duty is not usually one of
the applications showing the greatest energy savings from the
application of adjustable speed drives. Some energy savings may be
realized from adjustable speed drives, but they are usually quite modest
and economic justification is frequently marginal at best.)
Granted that the temperature of cool water is lower as is the viscosity,
so obviously longer running at reduced flow is possible, and lubricity
must also be greater.
Temperature is not the only concern. Low
flowrates in most pumps do hurt, by causing increased bearing wear due
to unbalanced hydraulic forces. Flows less than 60% of BEP are not
recommended by API, although with a VSD, the pump would not produce such
proportionally high unbalanced forces, since discharge pressure is
reduced.
Each pump having its own control valve does not ease the
situation. The pressure of the header (assumed to equal the highest
discharge pressure of any connected pump) must be reached by any other
pump in order for any other pump to discharge into that header. A pump
producing less pressure than the header pressure must have its own
discharge check valve in order to avoid being spun backwards by fluid
attempting to enter from the higher pressure header. Placing a control
valve betwen a pump discharging at a pressure lower than the header will
still not improve that situation. You could only close it in an
attempt to avoid backspin. Flow from the higher pressure header would
enter the even lower pressure at the control valve's outlet and still
attempt to backflow into the pump.
Additionally, when a
centrifugal pump is deadheaded its discharge pressure is deadheaded at
shutoff pressure, which is the same pressure, if it has a discharge
control valve or not. Deadhead pressure with a control valve is not
reduced and is in fact usually the maximum pressure that a centrifugal
pump can produce. And, power is not being expended on the fluid, except
for minor internal recirculation flows and all the rest of the power
used by the pump to overcome internal fluid, bearing and stuffing box
friction is being converted to heat. There is no possibility for
improvement by deadheading a pump at a lower pressure or any other
pressure other than its shutoff pressure,... without a VSD.
On
the other hand, a VSD driven pump, especially with recirculation, could
be used to lower the shutoff head corresponding to a lesser rpm, and
reducing the heat load. Even a VSD driven pump without recirculation
would produce less pressure and less heat. Total power consumption does
drop off with lesser flow at reduced discharge head, and since head
drops with the rpm^2, and flow drop is linear, a VSD w/ recirculation
can improve the heat load.
True there is less power consumption
at lower flows, with or without a control valve on a non VSD equipped
pump, but most all power delivered is converted to heat at the lesser
efficiency, so a lesser power consumption is paid for with increased
resulting temperature load to the pump.
It also don't think
that power consumption with a VSD drops, as you say, almost the same as
if flow is restricted with a valve (on a pump without a VSD). Power
consumption drops with the cube root of the pump speed on a VSD equipped
pump, but power consumption on a pump without a VSD looks like that on
any typical centrifugal pump curve with reducing flows, which is an
inverted curve that depends mostly on the pump's hydraulic efficiency at
flows away from BEP Q. Power consumption with a VSD dropping with the
cube root of rpm and with only a very slight change in efficiency at
different rpms and the same change in efficiency with flowrate as a
non-VSD equipped pump, would appear as a cubic curve and power
consumption drops very fast. I think those curves are very different,
however the power consumption of a VSD equipped pump with a control
valve, or a VSD equipped pump without a control valve would indeed be
equivalent. The control valve has no effect on power consumption of the
pump, as it mearly increases or decreases resisting head and
consequently only changes the power required to flow into the system at
any given control valve setting.
MORE NEWS