Yipump Valve Y13H-25 Internal Thread Pressure Reducing Valve: Pressure Range and Operation Manual
Pressure Range for the Y13H-25
The Y13H-25 has a nominal pressure of 2.5 MPa. Its shell test pressure is 3.75 MPa, and the seal test pressure is 2.5 MPa. The maximum inlet pressure is 2.5 MPa. The adjustable outlet pressure range is 0.1 MPa to 1.6 MPa, with a minimum pressure differential of 0.15 MPa between inlet and outlet required for stable regulation. Pressure characteristic deviation and flow characteristic deviation comply with GB12246-1989. The valve is intended for steam, water, and oil media, and its temperature capability depends on the body and trim materials selected; for steam service, the operating temperature should be confirmed against the specific material configuration before installation.The main pressure reducing valve product names of China Pressure Reducing Valve Network include:Piston Adjustable Reducing And Stabilized Valve,Self-regulative ValveTunable Pressure-reducing-and-maintaining Valve,YB Series Pressure-Reducing-Aad-Maintaining ValveY416X Type Direct-acting Spring diaphragm Reducing Valve.
Installation and Operation Manual
Installation must begin with flushing the entire pipeline to remove weld slag, scale, and debris that could obstruct the piston or damage the seat. The Y13H-25 should be mounted vertically in a horizontal pipeline, with the flow direction matching the arrow on the valve body; reverse installation will prevent proper regulation. A bypass line with a gate valve should be provided. Before startup, open the bypass to discharge condensate and steam-water mixture, reducing the risk of water hammer when the main valve begins to open. A strainer or filter should be installed upstream to protect the pilot mechanism from particulate matter.
For pressure adjustment, close the gate valve upstream of the reducing valve and open the downstream gate valve to create a low-pressure environment. Turn the adjusting screw counterclockwise to its uppermost position, then slowly open the upstream gate valve fully. Turn the adjusting screw clockwise gradually until the desired outlet pressure is reached, using the downstream pressure gauge as the reference. Tighten the lock nut to secure the setting, and open the downstream gate valve. If the outlet pressure overshoots the target during adjustment, restart from the first step and approach the setpoint from low pressure to high pressure only.
Do you still need to know or purchase the following pressure reducing valve products: